System Settings Menu
The system settings menu shows the Sensorbee Modbus Lite's RTU interface defaults — the values your Modbus host needs to match.
Factory defaults
| Parameter | Value |
|---|---|
| Type | Modbus RTU Slave |
| Insulation | Insulated or non-insulated (per order) |
| Baud rate | 9600 bit/s |
| Data bits | 8 |
| Parity | None |
| Stop bits | 2 |
| Modbus address | 1 (0x1) |

Changing values
The system settings menu currently surfaces the polling interval only. Other parameters (slave address, baud rate, parity, stop bits) live in the Modbus settings menu. Further system-level controls will be added in future firmware releases.
Parity / stop-bit constraint. If parity is set to None, stop bits must be 2. If parity is Even or Odd, stop bits must be 1. The firmware enforces this — it's a Modbus specification requirement.