System Settings Menu
The system and Modbus settings menus contain the settings for serial communication. An installation with Sensorbee external sensors normally works without any change.

Standard for external sensors
The Pro2 communicates with external sensors over Modbus RTU. The Sensorbee standard is 19200 bit/s, 8 data bits, even parity, 1 stop bit. Units and sensors that were delivered before this standard use 115200 bit/s, with the same parity and stop bit. Both are in use in the field, and both work.
If an external sensor does not answer, check that the unit uses the same baud rate as the sensor. You change the baud rate, parity and stop bits in this menu.
Settings
| Setting | Description |
|---|---|
| External sensor supply voltage | 5 V or 12 V, as the connected sensors need. Ask Sensorbee if you do not know which setting a sensor needs. |
| Serial settings for external sensors | Baud rate, parity and stop bits of the Modbus RTU connection to the external sensors. A change applies after a restart. |
| Modbus RTU output | For units that have a Modbus RTU output to a PLC, data logger or SCADA system. The unit then answers as a Modbus RTU server (slave). You set the address, baud rate and device name in the Modbus settings menu. Check the values in the menu before you connect your system. |
With no parity, the connection uses 2 stop bits. With even or odd parity, it uses 1 stop bit. The firmware sets this automatically, because the Modbus specification requires it.
The serial settings for external sensors and the sensor supply voltage selection require base unit firmware 3.39.0 or later.
The polling interval has its own menu: Polling interval.